CONDUITS
PART 1 GENERAL
1.01 GENERAL
A. PVC conduits shall generally be allowed in CAST-IN-SITU. Surface
installed Conduits (below or above false ceiling) shall be rigid steel (GI).
Where heavy protection against mechanical damage is required only rigid
steel (GI) conduit shall be used.
B All conduits and conduit fittings shall comply with concerned local
authorities Specifications
C In precast concrete slabs etc. GI conduit shall be used
D All conduits are fire retardant colored for all systems even if used in
concrete slabs.
1.02 CONDUIT SYSTEM
Conduit system shall be provided including all necessary fittings, supports,
Accessories, all other hardware complete as required.
For underground installation UPVC conduit shall be used
All materials for caulking and sealing conduits, pipes, sleeves etc through fire
rated Walls or floors, shall be approved by the concerned local authoritiesas
similarly applicable to cable trays and Trunking.
1.03 RELATED WORKS SPECIFIED ELSEWHERE
A. Section 16200 Cables & Wires
B. Section 16300 Supporting Devices
1.04 QUALITY ASSURANCE
A. Relevant British Standards
B. Concerned local authorities rules and regulations
C. Alternative codes and standards which will satisfy the engineer that the
material offered is of equal standard to that specified.