6. Sizes and types of protective devices.
7. Sizes and types of incoming and outgoing cables.
8. Contacts location references of relays and other control devices (if any).
B. Charts shall be typed on A4 size sheets. They shall be enclosed in a clear
plastic envelope and shall be securely fixed to the inside cover of the unit.
Additional copies of the charts shall be included in the Operation and
Maintenance Manuals.
2.05 CABLE IDENTIFICATION TAGS
A. All cables which exit from manholes, vaults, handholes, and
transformer or switch enclosures shall be properly tagged or labeled. Tags
shall be permanent, non-corrodible and clearly readable. Tags should include
the information listed below for the various circuit categories:
Primary Cables - 11 kV
Feeder Name
Voltage
Phase (for single conductor cables)
B. Cable identification tags for wire and cable circuits shall be of an opaque nylon
material arranged to include a marker plate, non-releasing nylon ties, and cable
fastening tail. One side shall be roughened to hold black nylon permanent ink.
Identification shall be permanent and waterproof. The holding device shall be
designed to allow the fastening tail to pass around the cable through the holding
device, and prevent removal of the tail without cutting it loose from the marker.
Cable identification shall be inscribed in Arabic and English.
2.06 CABLE WARNING TAPES
A. For buried LV and HV cables use warning tapes according to the standard practice
of Electricity Supply Authority and applicable international standards.
B. Cable warning tapes shall be of polythene, not less than 150 mm wide and at least
0.25 mm thick. They shall be yellow in color for LV and MV cables and bear the
continuously repeated legend “CAUTION ELECTRIC CABLE BELOW” or
similar in English and Arabic, in black letters not less than 30 mm high.